Description
Mitsubishi PLC-FX2N-64MR FX2N series Mitsubishi PLC is compact device with built in I/O’s offer offer’s extremely fast programming execution and provide maximum flexibility. Mitsubishi PLC-FX2N-64MR has 64 built in I/O points can expendable up to 256 points, 32 digital inputs and 32 relay type outputs. Relay outputs rated 240VAC or 30 VDC up to 2 Amp per point max. 24Vdc which can configure sink/source. 8k program capacity 27 basic instructions.60 Hz high speed counters and real time clock are available. Built in run/stop switch is available. High processing speed, 0.08μs/basic instruction 125 applied instructions, 3072 auxiliary relays, 256 timers, 235 counters. 8000 data registers.
World Automation and Engineering is the biggest sealer of Mitsubishi PLC and accessories in Bangladesh. We have whole sale and retail both convenience method to purchase your best deal. We provide 12 months warranty on our every product and also provide after sale support and services. Delivery service are also available via courier, we deliver our product via Sundarban Courier Service and SA Paribahan all over Bangladesh. For requirement of any other information feel free to contact With WhatsApp. WhatsApp No: +88 01759 659025.
Product Specification of Mitsubishi PLC-FX2N-64MR:
| Model | FX2N-64MR |
| Digital Input | 32 point |
| Digital Output | 32 Point |
| Output Type | Relay |
| Supply Voltage | 100-240VAC |
| Power Consumption | 60VA |
| Shipping Weight | 3 Kg |
| Communication Port Type: |
RS232, RS422, RS485. |
| Program Capacity: |
8000 Steps |
| Programming Interface: | Computer, GX-Developer, GX Works2 |
| Maximum Operating Temperature: | +55°C |
| Dimensions: | 90 x 220 x 87 mm |
| Battery Backup: | Yes |
| Mounting Type: | DIN Rail |
Performance Specification of The FX2N(C):
| Item | Specification | Remarks | |
| Operation control method | Cyclic operation by stored program | ||
| I/O control method | Batch processing method (when END instruction is executed) | I/O refresh instruction is available | |
| Operation processing time | Basic instructions: 0.08 µs Applied instructions: several 10’s to 100 µs | ||
| Programming language | Relay symbolic language + step ladder | Step ladder can be used to produce an SFC style program | |
| Program capacity | 8000 steps built in | Expandable to 16000 steps using additional memory cassette | |
| Number of instructions | Basic sequence instructions: 20 Step ladder instructions: 2 Applied instructions: 125 | A Maximum 125 applied instructions are available | |
| I/O configuration | Max hardware I/O configuration points 255, dependent on user selection (Max. software addressable Inputs 255, Outputs 255) | ||
| Auxiliary relay (M coils) | Genera | 3072 points | M0 to M3071 |
| Latched | 2572 points (subset) | M0 to M3071 | |
| Special | 256 points | From the range M8000 to M8255 | |
| State relays (S coils) | General | 1000 points | S0 to S999 |
| Latched | 500 points (subset) | S500 to S999 | |
| Initial | 10 points (subset | S0 to S9 | |
| Annunciator | 100 points | S900 to S999 | |
| Timers (T) | 100 msec | Range: 0 to 3,276.7 sec 200 points | T0 to T199 |
| 10 msec | Range: 0 to 327.67 sec 46 points | T200 to T245 | |
| 1 msec retentive | Range: 0 to 32.767 sec 4 points | T246 to T249 | |
| 100 msec retentive | Range: 0 to 3,276.7 sec 6 points | T250 to T255 | |
| Counters (C) | General 16 bit | Range: 1 to 32,767 counts 200 points | C0 to C199 Type: 16 bit up counter |
| Latched 16 bit | 100 points (subset) | C100 to C199 Type: 16 bit up counter | |
| General 32 bit | Range: -2,147,483,648 to 2,147,483,647 35 points | C200 to C234 Type: 32 bit up/down counter | |
| Latched 32 bit | 15 points (subset) | C219 to C234 Type: 16 bit up/down counter | |
| High speed counters (C) | 1 phase | Range: -2,147,483,648 to +2,147,483,647 counts General rule: Select counter combinations with a combined counting frequency of 20kHz or less. Note all counters are latched | C235 to C240 6 points |
| 1 phase c/w start stop input | C241 to C245 5 points | ||
| 2 phases | C246 to C250 5 points | ||
| A/B phase | C251 to C255 5 points | ||
| Data registers (D) | General | 8000 points | D0 to D7999 Type: 16 bit data storage register pair for 32 bit device |
| Latched | 7800 points (subset) | D200 to D7999 Type: 16 bit data storage register pair for 32 bit device | |
| File registers | 7000 points | D1000 to D7999 set by parameter in 14 blocks of 500 program steps Type: 16 bit data storage register | |
| Special | 256 points | From the range D8000 to D8255 Type: 16 bit data storage register | |
| Index | 16 points | V0 to V7 and Z0 to Z7 Type: 16 bit data storage register | |
| Pointers (P) | For use with CALL | 128 points | P0 to P127 |
| For use with interrupts | 6 input points, 3 timers, 6 counters | I00 to I50 and I6 to I8 (rising trigger =1, falling trigger =0, =time in msec) | |
| Nest levels | 8 points for use with MC and MCR | N0 to N7 | |
| Numbers | Decimal K | 16 bit: -32,768 to +32,767 32 bit: -2,147,483,648 to +2,147,483,647 | |
| Hexadecimal H | 16 bit: 0000 to FFFF 32 bit: 00000000 to FFFFFFFF | ||
| Floating Point | 32 bit: 0, ±1.175 x 10-38, ±3.403 x 1038 (Not directly enterable) | ||