Description
Mitsubishi PLC-FX1N-40MR is FX1N series PLC Brand Mitsubishi, This PLC has 40 built in I/O. 24 inputs and 16 outputs relay type. Operating input voltage 100 to 240 VAC. This advance FX series PLCs is compact device offer extremely fast programming execution up to eight function modules and provide maximum flexibility. It has expendable I/O feature up to 256 I/O high processing speed 0.08μs. 3072 auxiliary relays, 256 timers, 235 counters. 8000 data registers 8K step RAM program memory (expandable to 16K with EEPROM), 125 applied instructions. 24 Vdc 460mA output for sensors etc. with older FX units. Mitsubishi PLC-FX1N-40MR is use with FX1S, FX1N and FX2N PLC. DIN rail mount and are 90 mm high and 87 mm deep. We provide all kind of industrial automation product with good quality and reasonable price. 12 months warranty available. We provide committed support and service. Wholesale and retail convenience are available.
For more Related Products: Click here
Product Specification: Mitsubishi PLC-FX1N-40MR
| Model | FX1N-40MR |
| Unit type | M = MPU-main unit |
| Digital inputs | 24 |
| Digital Outputs | 16 |
| Output Type | Relay |
| Power Supply | 100-240 VAC |
| Power consumption |
32W |
| Shipping Weight | 2 Kg |
| Operating Temperature | 0 to 55 °C (32 to 131 °F) |
| Storage Temperature | -20 to 70 °C (-4 to 158 °F) |
| Operating Humidity | 35 to 85% Relative Humidity, No condensation |
| Noise Immunity | 1000 Vp-p, 1microsecond, 30 – 100 Hz, tested by noise simulator |
| Ground | Class D grounding (grounding resistance: 100 Ω or less) |
| Certification | UL/cUL (UL508) |
Product Outline:

FX1N-40MR outline
- Top cover
- Direct mounting holes (4.5 mm <0.17″> diameter)
- I/O terminal block securing screws
- Input terminals (24V DC) and power supply terminals
- Input LED status indicators
- Expansion port cover
- PLC status indicators (POWER, RUN, ERROR)
- Output LED status indicators
- DIN rail mounting clip
- Output terminals and power supply source terminals
- Optional equipment connector
- Expansion port
- Run/Stop switch
- Variable analog potentiometers. Upper pot, D8030 read from VR1. Lower pot D8031 read from VR2






Reviews